Fire protection

Michigan Administrative Code

Section: 29.7059

Jurisdiction: MI

Bluebook Citation: Mich. Admin. Code r. 29.7059

Rule 59. Section 6-4 of the storage and handling of gaseous and Liquefied H2 code is added as follows: 6-4 A portable fire extinguisher having a rating of not less than 40-B:C, or 2 20-B:C, shall be located within 75 feet (22.9 meters) from the pumps, dispensers, and container fill openings. Fire extinguishers shall be inspected and maintained according to NFPA 10, "standard for portable fire extinguishers," adopted by reference in section 8-1.1.

History: 2008 AACS.